Serial NumberprojectMS4-05MS4-06
1Rated voltage, kV1212
2Rated current, A12501250
3Rated power frequency withstand voltage, kV4242
4Rated impact withstand voltage, kV8585
5Rated short-circuit breaking current, kA2531.5
6Rated short-circuit making peak current, kA6380
7Rated short-time withstand current, kA6380
8Rated short-time withstand time, s44
9Rated frequency, Hz5050
10Phase spacing, mm----
11Contact gap, mm8±0.58±0.5
12Overtravel of the mechanism, mm2±0.52±0.5
13Rated operating cycleO-0.3s-CO-15s-COO-0.3s-CO-15s-CO
14Inherent closing time, ms<25<25
15Three-phase closing asynchronously, ms----
16Close-in bounce time, ms≤2≤2
17Inherent tripping time, ms5±0,55±0,5
18The three-phase tripping was not synchronized, ms----
19Mechanical life, cycles5000050000
20Electrical life (rated short-circuit current), times5050
21Number of auxiliary switches3NO+2NC3NO+2NC
22Weight, kg1414












ONLINE MESSAGE

Please fill in a valid email address
Captcha Can not be empty

RELATED PRODUCTS

No search results found!

Contact Information

Indiana Office

58Huaxing Road, industrial zone, Weng L ong Street Yueqing City, Zhejiang province, China.

+86-136-9571-0067

ansel@apexe.cc

Search

Insulation Accessories,Vacuum Circuit Breaker,Switchgear,High Voltage Electrical Equipment,Switchgear Fittings,Earthing Switch

This website uses cookies to ensure you get the best experience on our website.

Accept Reject